Physical Modeling of Heated Discharges into a Stagnant River

See related content

by Patrick J. Ryan, Bechtel Civil Inc,
Adnan Alsaffar, Bechtel Civil Inc,
Mohamed Gasser, Bechtel Civil Inc,
Ibrahim Dessouki, Bechtel Civil Inc,
Ahmed Abdel Halim, Bechtel Civil Inc,

Document Type: Proceeding Paper

Part of: Hydraulic Engineering:

Abstract: An alternative cooling system study was performed for the Damietta Combined Cycle Plant in Egypt. The alternatives included spray canals, helper cooling tower and once-through cooling. Factors such as capital and operating costs, maintenance and limited space on the site, led to rejection of the first two alternatives and the selection of once-through cooling. An important factor in the study was the effect of near zero river flow on the mixing zone size and on the recirculation into the intake. Analytical and physical model studies were performed to optimize the location and configuration of the intake and discharge structures.

Subject Headings: Hydrologic models | Physical models | Water discharge | Model analysis | Rivers and streams | Water intakes | Hydraulic models | Optimization models | Structural models | Africa | Egypt

Services: Buy this book/Buy this article


Return to search